Customization: | Available |
---|---|
After-sales Service: | Factory Warranted |
Warranty: | 1 Year or 1000 Running Hours |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1. GENERATOR DATA
Voltage Available:
50Hz: 380-400-415V/220-230-240V;
60Hz: 220-380-416-440-480V/110-208-220-240V
Any special voltage is also available as client's request
Prime Power:
Comply with GB/T2820-97(eqv.ISO8528).
Genset can run unlimitedly under certain power range.
One hour 10% over load in every 12 running hours is allowed;
Standby Power:
standby power is the limit value of maximum output for emergency use.
It is off-oil power,overloading is prohibited
2. MAIN SPECIFICATION
Model | Prime output(kw/kva) |
Standby output(kw/kva) | Engine model | Alternator model |
KP206-HG | 150/187.5 | 165/206 | YC6TD-HG | STF-274H |
Genset Data | Size & Weight (Open type) | 3600*1400*2000mm (3300kgs) | ||
Frequency | 50Hz | |||
Standard Features | Radiator 50OC max,fans are driven by belt, with safety guard/Ripple flex exhaust pipe, exhaust siphone, flange, muffler | |||
Voltage | 415/240V | |||
Phase & wires | 3phase, 4wires | |||
Power factor | COSΦ=0.8 (lagging) | |||
Battery | 24V | |||
Fuel Valve | Supersonic injection valve | |||
Breaker | Schneider | |||
Engine Data |
Brand & Model | Yuchai YC6TD-HG | ||
Cycle | 4 stroke | |||
Engine power (kwm) | 180 | |||
Air intake way | Turbo | |||
Governor | Electronic | |||
Cylinder | 6 | |||
Bore*Stroke (mm) | 152*180 | |||
Displacement (L) | 19.6 | |||
Control system | ECI | |||
Compression Ratio | 11:1 | |||
Combustion system | Direct injection | |||
Speed | 1500RPM | |||
Cooling way | Water cooled | |||
Alternator Data |
Brand & Model | Kanpor STF-274H | ||
Alternator Power | 150KW | |||
Frequency & Speed | 50Hz, 1500RPM | |||
phase & Voltage | 3 phases 4 wires & 415/240V | |||
System | Brushless AC Synchronous, Single bearing | |||
Insulation & Protection | H, IP44 | |||
Voltage Regulator | Standard AVR | |||
Control System |
Brand & Model | ComAp InteliLite NT MRS 10 | ||
Two language interface: Chinese/English | ||||
Start or Stop Generator set manually / automatically; Open controller output can be defined as Pre-heat/Idle output. | ||||
High Coolant temperature protection; Low Oil pressure protection. Over speed protection | ||||
Over load protection; Generator over/under frequency protection: Generator over/under/unbalance voltage protection |
3. PRODUCT FEATURES
(1).Full control panel with power indicator light and oil light.
(2).Emergency shutdown for low oil pressure and high water temperature.
(3).Large fuel tank ensure continuous running.
(4).Low noise & vibration.
(5).Compact structure.
(6).Reliable performance.
(7).Easy for installation and maintenance.
(8).50Hz and 60Hz both are available for choice