Basic Info.

Model NO.
KPYD45
Conditions of Use
Land Use
Usage
Common Units, Standby Unit, Emergency Crew
Landuse Type of Unit
Low Noise
Excitation Mode
AC Rotating Exciter
Certificate
Ce ISO SGS Soncap TUV
Voltage
220V/127V 380V/220V 400V/230V 415V/240V 480V/277V
Current
60.8A
Engine Model
Y4102zd
Transport Package
Plywood Case
Specification
2100x1000x1200mm
Trademark
Kanpor
Origin
Fujian, China(Mainland)
HS Code
8502110000
Production Capacity
300PCS Per Month

Product Description

Yangdong 32kw 40kVA (36kw 45kVA) Canopy Type Diesel Genset

1. GENERATOR DATA                               

Voltage Available: 

50Hz: 380-400-415V/220-230-240V;

60Hz: 220-380-416-440-480V/110-208-220-240V

Any special voltage is also available as client's request

Prime Power: 

Comply with GB/T2820-97(eqv.ISO8528).

Genset can run unlimitedly under certain power range.

One hour 10% over load in every 12 running hours is allowed;

Standby Power:

standby power is the limit value of maximum output for emergency use.

It is off-oil power,overloading is prohibited

2. MAIN SPECIFICATION                        

Genset Model   KPYD33 KPYD38 KPYD45 KPYD55 KPYD66
Rated Power KW/KVA 24/30 27/33.8 32/40 40/50 48/60
Standby Power KW/KVA 27/33 30/38 36/45 44/55 52.8/66
Rated Voltage V 220V/127V 380V/220V 400V/230V 415V/240V 480V/277V 600V/346V
Speed RPM 1500/1800
Rated frequency Hz 50/60
Engine Model   Y4100D Y4102D Y4102ZD Y4102ZLD Y4105ZLD
Engine Power KW 30 33 40 48 55
Air intake way   Natural Natural Turbo Turbo Turbo
Governor   Electronic Electronic Electronic Electronic Electronic
Cylinder QTY 4 4 4 4 4
Bore*Stroke mm*mm 100×118 102×118 102×118 102×118 105×118
Displacement L 3.707 3.857 3.857 3.857 4.1
Fuel Consumption g/kw.h 223 220 220 220 220
Compression Ratio   18:1 18:1 18:1 18:1 18:1
Alternator Model   STF-184G STF-184H STF-184J STF-224D STF-224E
Voltage Regulation   AVR
Excitation Method   Brushless
Open Type Size mm 1650x800x1050 1700x800x1100 1700x800x1100 1900x850x1200 1900x850x1200
Open Type Weight kg 820 850 900 980 1080
Soundproof Size mm 2000x950x1150 2100x1000x1200 2100x1000x1200 2300x1050x1250 2300x1050x1250
Soundproof Weight kg 1050 1080 1180 1320 1480

3. PRODUCT FEATURES

(1).Full control panel with power indicator light and oil light.

(2).Emergency shutdown for low oil pressure and high water temperature.

(3).Large fuel tank ensure continuous running.

(4).Low noise & vibration.

(5).Compact structure.

(6).Reliable performance.

(7).Easy for installation and maintenance.

(8).50Hz and 60Hz both are available for choice
Yangdong 32kw 40kVA (36kw 45kVA) Canopy Type Diesel Genset
Yangdong 32kw 40kVA (36kw 45kVA) Canopy Type Diesel Genset
Yangdong 32kw 40kVA (36kw 45kVA) Canopy Type Diesel Genset
Yangdong 32kw 40kVA (36kw 45kVA) Canopy Type Diesel Genset
Yangdong 32kw 40kVA (36kw 45kVA) Canopy Type Diesel Genset

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now