Customization: | Available |
---|---|
Type: | Self-Starting Diesel Generator |
Installation Method: | Fixed |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1. GENERATOR DATA
Voltage Available:
50Hz: 380-400-415V/220-230-240V;
60Hz: 220-380-416-440-480V/110-208-220-240V
Any special voltage is also available as client's request
Prime Power:
Comply with GB/T2820-97(eqv.ISO8528).
Genset can run unlimitedly under certain power range.
One hour 10% over load in every 12 running hours is allowed;
Standby Power:
standby power is the limit value of maximum output for emergency use.
It is off-oil power,overloading is prohibited
2. MAIN SPECIFICATION
Powered by Cummins engine
Engine Model |
6BT5.9-G2 |
Number of Cylinders |
6 cylinders in line |
Cycle |
4 stroke |
Aspiration |
Turbocharged and after water cooled |
Bore×Stroke |
102mm x120mm |
Displacement |
5.9L |
Compression ratio |
17.5:1 |
Prime Power/Speed |
86KW / 1500rpm |
Standby Power/Speed |
92KW / 1500rpm |
Speed Governor |
Electrical |
Cooling System |
Forced water cooling cycle |
Steady speed droop |
≤1% |
Total lubrication system capacity |
16.4L |
Coolant capacity (engine only) |
9.1L |
Fuel Consumption at 100% Load |
214g/kw.h |
Starter Motor |
DC24V, |
Alternator |
DC24V |
Coupled with Stamford alternator (3 years' warranty)
Alternator Model |
UCI274C |
Prime power |
80KW |
Frequency/speed |
50HZ/1500rpm |
Exciter type |
Single bearing, Brushless, Self-excited |
Power factor |
0.8 |
Voltage adjust range |
≥5% |
Voltage regulation NL-FL |
≤±1% |
Insulation Grade |
H |
Protection Grade |
IP23 |
Phase |
Three phases |
100KVA diesel generator, the control panel we can use ComAp IL9, ComAp MRS10, ComAp AMF20 or AMF25, SmartGen HGM6110N or HGM6120N, DeepSea DSE6020 and DSE7320
Model |
MRS10/DSE6020/HGM6110N... |
The control module gives digital readouts of: Generator voltage; Output frequency; Engine speed; Battery voltage; Engine hours run. The control module has indicators for failure information: Overspeed/underspeed, Emergency stop Low oil pressure; High water temperature Failure to start Battery charger failure Automatic shutdown occurs under: Low engine oil pressure; High engine water temperature; Overspeed/underspeed; Failure to start after three attempts. |
Standard Accessories |
Open type |
Silent type |
Sound-proof & Weather-proof Canopy |
N/A |
√ |
Daily base fuel tank. 8 hours capacity |
N/A |
√ |
Single-bearing generator again drops |
√ |
√ |
Intelligent LED display control panel |
√ |
√ |
Speed governor |
√ |
√ |
Electric start and 24v charger |
√ |
√ |
Standard air filter, oil filter, fuel filter |
√ |
√ |
Cooling water tank |
√ |
√ |
High-efficient silencer. |
√ |
√ |
Exhaust elbow |
√ |
√ |
Storage battery |
√ |
√ |
Steel base-frame against vibration |
√ |
√ |
Soft pipe for fuel and handle for lube going-out |
√ |
√ |
Operation& Maintenance manual. |
√ |
√ |
(1).Full control panel with power indicator light and oil light.
(2).Emergency shutdown for low oil pressure and high water temperature.
(3).Large fuel tank ensure continuous running.
(4).Low noise & vibration.
(5).Compact structure.
(6).Reliable performance.
(7).Easy for installation and maintenance.
(8).50Hz and 60Hz both are available for choice